Minds → HVAC → What certification standards must refrigerant recovery and recycling equipment meet under 40 CFR 82.158 before a technician can use it on the job? Answer in under 100 words.
US FederalEPA40 CFR Part 82 Subpart F (Clean Air Act Section 608)

What certification standards must refrigerant recovery and recycling equipment meet under 40 CFR 82.158 before a technician can use it on the job? Answer in under 100 words.

Starting January 1, 2017, § 82.158 governs recovery and/or recycling equipment used on appliances and prohibits manufacturing or importing such equipment unless it is certified under the section. By build date: B1 (ARI 740-1993) covers Nov 15, 1993–Sep 21, 2003; B2 (ARI 740-1995) covers Sep 22, 2003–Dec 31, 2016; B3 (non-flammable) or B4 (flammable) covers Jan 1, 2017 onward. Machines must achieve the Table 2 evacuation levels for their appliance category, and technicians must use equipment certified pursuant to § 82.158.
Last verified: 2026-08-26 · Sources checked: 4/4 resolving · Next scheduled review: 2026-11-24

Details / How it works

  • Starting January 1, 2017, § 82.158 governs recovery and/or recycling equipment used on appliances and prohibits manufacturing or importing such equipment unless it is certified under the section.
  • Manufacturers and importers must have equipment built on or after November 15, 1993 certified by an approved equipment testing organization.
  • By build date: B1 (ARI 740-1993) covers Nov 15, 1993–Sep 21, 2003; B2 (ARI 740-1995) covers Sep 22, 2003–Dec 31, 2016; B3 (non-flammable) or B4 (flammable) covers Jan 1, 2017 onward.
  • Appendix B3 is based on AHRI Standard 740-2016.
  • An approved equipment testing organization is one approved by the EPA Administrator pursuant to § 82.160.
  • Machines must achieve the Table 2 evacuation levels for their appliance category, and technicians must use equipment certified pursuant to § 82.158.
  • Certified units must carry a durable label naming the certifying organization and appliance category, plus manufacture date and serial number.
  • Manufacturers or importers must retest or inspect certified equipment at least every three years, and EPA may revoke certification if a model line later fails the criteria.
  • Units with a noncondensables purge device may vent no more than 3 percent of recycled refrigerant, and hoses must use low-loss fittings.

Numbers & thresholds

For small appliances, recovery equipment must recover 90 percent of the refrigerant with the compressor operating or 80 percent with it inoperative, or achieve a four-inch vacuum.

Parameter Standard Applies to
Rules effective January 1, 2017 All covered recovery/recycling equipment
Test protocol Appendix B1 (ARI 740-1993) Built Nov 15, 1993 – Sep 21, 2003
Test protocol Appendix B2 (ARI 740-1995) Built Sep 22, 2003 – Dec 31, 2016
Test protocol Appendix B3 (non-flammable, AHRI 740-2016) / Appendix B4 (flammable) Built on/after Jan 1, 2017
Evacuation target Table 2 levels (by pressure class and charge size) Non-small, non-MVAC appliances
Small-appliance recovery 90% (compressor on) / 80% (compressor off), or 4-in. Hg vacuum Small appliances
MVAC-like gear, pre-1993 102 mm Hg vacuum MVAC-like appliances
Purge loss cap ≤ 3% of refrigerant recycled Units with purge devices
Retesting cadence At least every 3 years Manufacturers/importers

Exceptions & edge cases

  • Equipment built before November 15, 1993 (except small appliances, MVACs, and MVAC-like appliances) is grandfathered as certified if it reaches its Table 2 evacuation level when checked with a properly calibrated pressure gauge.
  • Altering a certified unit's design triggers resubmission for certification testing, and the altered equipment counts as uncertified until it passes.
  • MVAC and MVAC-like recovery equipment is certified under subpart B of Part 82, with pre-November 15, 1993 MVAC-like gear required to reach 102 mm Hg vacuum.
  • System-dependent recovery equipment cannot be used on appliances charged with more than 15 pounds of refrigerant unless it is permanently attached as a pump-out unit.
  • Per § 82.154(b), no one may maintain, service, repair, or dispose of an appliance containing regulated refrigerants without using equipment certified for that refrigerant and appliance type under § 82.158.

Sources

  1. [1]U.S. National Archives, Electronic Code of Federal Regulations — 40 CFR 82.158 — Standards for recovery and/or recycling equipment · as of 2026-08-26
  2. [2]U.S. National Archives, Electronic Code of Federal Regulations — 40 CFR 82.156 — Proper evacuation of refrigerant from appliances · as of 2026-08-26
  3. [3]U.S. National Archives, Electronic Code of Federal Regulations — 40 CFR 82.152 — Definitions · as of 2026-08-26
  4. [4]U.S. National Archives, Electronic Code of Federal Regulations — 40 CFR 82.154 — Prohibitions · as of 2026-08-26

Ask this MIND

This answer is static and source-locked. Ask HVAC your version of this question.

Related questions

This is general information, not advice. HVAC summarizes primary sources (EPA, DOE, ENERGY STAR) as of the dates shown. It is not tax/legal/immigration advice and doesn’t account for your situation. Consult a qualified professional before acting. About this MIND